Help
Compel Groupgroup

Wire Size Calculator

Author: Emma Clarke, Reference Desk5 min readReviewed

A 60 amp circuit needs 6 AWG copper at the 75 degree C rating. 30 amp takes 10 AWG, 50 amp takes 8 AWG and 100 amp takes 3 AWG. A 200 amp feeder needs 3/0 copper under the general table, though a dwelling service carrying the whole load may use 2/0. On runs over about 30 metres, go up a size to keep voltage drop under 3 percent.

Electrical. Based on NEC 310.16, NEC 240.4(D), NEC 310.12.

Wire size calculator

Enter the load, the one-way run length and the voltage. This returns the gauge that satisfies both ampacity and a 3 percent voltage drop, and tells you which of the two set the answer.

It sizes copper conductors at the 75 degree C column, which is what terminations on most equipment are rated for even when the cable insulation is rated higher.

Copper conductor
8 AWG

Governed by ampacity. Voltage drop over this run is 3.9 V, or 1.6 percent.

Copper at the 75°C column of NEC 310.16, three current-carrying conductors, 30°C ambient, 3 percent voltage-drop target. This is the general table, not the reduced NEC 310.12 dwelling-service allowance. Check local rules and derate for ambient temperature, conduit fill and continuous loads.

AWG chart and ampacity

The three columns are insulation temperature ratings. Use the 75 degree C column in practice: even with 90 degree C cable, the terminal blocks and breakers at each end are usually only listed to 75, and the lowest-rated part of the circuit governs.

The 90 degree C column is for derating calculations, not for picking a conductor outright.

NEC 310.16 ampacity for copper conductors, not more than three current-carrying conductors in a raceway, 30 degree C ambient.
AWGmm²60°C75°C90°C
142.08152025
123.31202530
105.26303540
88.37405055
613.3556575
421.2708595
326.785100115
233.695115130
142.4110130145
1/053.5125150170
2/067.4145175195
3/085.0165200225
4/0107.2195230260

Wire size by breaker rating

This is the answer most people are actually after. Note the small-conductor rule in NEC 240.4(D): regardless of what the ampacity table says, 14 AWG is limited to a 15 amp breaker, 12 AWG to 20 amp and 10 AWG to 30 amp. That rule overrides the higher figures in the 75 and 90 degree columns.

These are the general NEC 310.16 sizes and they apply to feeders, subpanels and branch circuits. Do not use the reduced dwelling-service figures here by mistake.

Copper and aluminium conductors by circuit rating, NEC 310.16 at 75 degree C terminations.
BreakerCopperAluminiumTypical use
15 A14 AWG12 AWGLighting circuits
20 A12 AWG10 AWGGeneral socket circuits
30 A10 AWG8 AWGDryer, small welder, compressor
40 A8 AWG6 AWGRange, larger compressor
50 A8 AWG6 AWGWelder, EV charger
60 A6 AWG4 AWGSubpanel, workshop feed
100 A3 AWG1 AWGSubpanel
125 A1 AWG2/0 AWGSubpanel
150 A1/0 AWG3/0 AWGLarge subpanel
200 A3/0 AWG250 kcmilFeeder

The dwelling-service exception

A single-family dwelling service, or a feeder carrying the entire load of one dwelling, is allowed smaller conductors under NEC 310.12 than the general table requires. This is why a 200 amp house service is commonly run in 2/0 copper rather than the 3/0 the general table would demand.

The allowance is specific. It applies to the service or feeder carrying the whole dwelling load and nothing else. Using these sizes on a workshop subpanel, a commercial feeder or any circuit that is not the full dwelling load is a code violation and an undersized conductor.

NEC 310.12 reduced sizes, dwelling services and full-load feeders only.
Service ratingCopperAluminium
100 A4 AWG2 AWG
125 A2 AWG1/0 AWG
150 A1 AWG2/0 AWG
200 A2/0 AWG4/0 AWG

Voltage drop on long runs

Ampacity is about the cable not overheating. Voltage drop is about the equipment at the far end actually working, and on a long run it is voltage drop that decides the size.

For a single-phase copper run the formula is VD = 2 x K x I x L / CM, where K is 12.9 for copper, I is the current, L is the one-way length in feet and CM is the circular mil area of the conductor. Aim for 3 percent or less on a branch circuit and 5 percent total including the feeder.

A practical shortcut: on runs past about 30 metres, go up one gauge. Past 60 metres, go up two.

Emma Clarke, Reference Desk editor at Compel GroupEmma ClarkeReference Desk

Emma looks after the reference charts and calculators. Every figure is copied from the named standard on the page rather than generated, and each page shows the date it was last checked. When a value looks wrong, the standard wins and the page gets fixed.

Share
Add Compel Group as a preferred source on Google

Reference

Wire Size Calculator questions

What size wire do I need for 60 amps?
6 AWG copper at the 75 degree C rating, or 4 AWG if you are running aluminium. On a run longer than about 30 metres, step up to 4 AWG copper to hold voltage drop under 3 percent.
What gauge wire for a 50 amp circuit?
8 AWG copper or 6 AWG aluminium. This is the usual size for a welder outlet or an EV charger. Longer runs want 6 AWG copper.
Can I put a 20 amp breaker on 14 AWG wire?
No. NEC 240.4(D) caps 14 AWG at 15 amps no matter what the ampacity table shows, because the small-conductor rule accounts for the way thin conductors behave under fault and overload. The same rule caps 12 AWG at 20 amps and 10 AWG at 30.
Why does the ampacity table have three temperature columns?
They are insulation ratings. In practice you size from the 75 degree C column, because breakers and terminal blocks are usually only listed to 75 degrees and the whole circuit is governed by its lowest-rated component. The 90 degree column exists for derating maths, not for picking a size directly.
Does run length change the wire size?
Often, yes. Ampacity does not care about length but voltage drop does. Beyond roughly 30 metres a circuit sized purely on amps will drop more than 3 percent, and motors and heaters both suffer for it. Go up a gauge past 30 metres and two past 60.
What size wire for a 200 amp service?
3/0 copper under the general NEC 310.16 table. A single-family dwelling service, or a feeder carrying that whole dwelling load, may use 2/0 copper or 4/0 aluminium under NEC 310.12. That reduction applies only to the dwelling service or full-load feeder, never to a subpanel or a commercial feeder.

Related reference tools